Dickson - WT540

Ethernet Temperature Data Logger

Place these data loggers throughout your facility and receive all data automatically at your PC. 
No retrieving data from loggers.  This is the easiest and most cost-effective way to
create a scalable monitoring network. 

  • Email and Text alerts available
  • Eliminates the need to change charts and pens
  • Data automatically downloaded to your computer wirelessly
  • Loggers continue to log in the event of a power outage

These loggers, while wired, are compatible with the WiZARD2 monitoring system
and software. Use them in conjunction with your WiZARD2 system or without! They allow you
to monitor locations that would have previously been cost prohibitive to monitor wirelessly.


Specification

 

Alarm Type

High/Low, Low Battery, Calibration Due, Lost Communication

Ambient Operating RH Temperature Conditions

0-95% RH non-condensing (Logger only)

Approvals

RoHS, FCC Part 15 Compliance, CE

Ambient Operating Temperature Conditions

-22 to 122F (-30 to 50C)

Battery Backup

4 AA Batteries

Battery Life (Avg)

6 Months (at 2 Minute Sample Rate in Moderate Conditions)

Cable Details

USB - Male Series A plug to 5 pin Male Series B mini plug.

Channels

CH1: Temperature, CH2: Temperature

Calibration Options

N100 , N300, N400, & N520

Data Capacity

32,000 (16,000 per channel)

Dimensions

1.7 x 4.25 x 4.25in

Download Type

Wireless

Enclosure

Black; ABS Plastic Clam Shell

Included Accessories

USB Cable, AC Adapter, 4 AA Batteries, Quick Start Guide

Mounting Options

Free Standing or Wall Mount (With Keyhole)

Network Requirements

If Host PC and Logger are on separate subnets, both Logger and Host PC subnets must be able to see each other. For best results, assign a fixed IP Address to the Host PC. If preferred, logger can be setup using DHCP (contact Dickson Technical Support for

Note on Alarm Type

All alarm conditions will generate a pop-up notification in the Dickson WiZARD Software. Text/Email notification available with use of WiZARD SECURE Software.

Power Source

120 to 240 VAC, 12 VDC (INTL fittings available)

Power Source Input

AC 100-240 0.5V 60/50 Hz

Power Source Output

DC 9V, 1A

Power Status Indicator

Red/Green/Blue (RGB) LED

PC Requirements

Minimum of 1 GB RAM; Windows XP (with service pack 3), Vista and Windows 7; 2 available USB ports

Sample Interval

User Selectable (from 10 seconds to 1 hour in 10 second intervals)

Software Options

W2 Version 1.2.0.11 or higher

Storage Conditions

-22 to 158F (-30 to 70C)

Storage Conditions RH

0-95% RH non-condensing

Temperature Accuracy

+/-1.8F from -22 to 122F (+/-1C from -30 to 50C)

Unit Weight

3 lb

Warranty

12 Month Limited



Product added : May 07 2012 07:18:49 AM